API 598 Pressure Testing: What Stainless and Carbon Steel Valves Must Pass
Most valve rejections at site are not design failures. They are arguments about a test certificate: what was tested, at what pressure, for how long, and against which leakage limit. API 598 is the document that settles those arguments, and it is worth reading before the purchase order rather than after the shipment.
The standard covers three separate tests. They answer three different questions, and a valve can pass one while failing another.
Three Tests, Three Different Questions
The shell test pressurises the body with the valve partly open and both ends blanked. It proves the pressure boundary — body, bonnet joint, gland area — holds. It says nothing about whether the valve closes.
The closure test, also called the seat test, closes the valve and pressurises one side. It proves the seat seals. It is run twice in most specifications: once with liquid at high pressure, once with air or nitrogen at low pressure.
The backseat test opens the valve fully, loosens the packing gland and pressurises the body. It proves the stem-to-bonnet seal works, which is what allows packing to be replaced on a live line.
A gate valve that passes the shell test and fails the closure test is a perfectly normal outcome. The body was never the problem.
It is also worth being clear about what this standard is not. API 598 is a production test on every valve, not a design qualification. It does not prove the valve will hold at 400 °C, survive thermal cycling, or seal after ten thousand cycles. Those are type-test and qualification questions, covered by fire-safe, cryogenic and cycle-life standards. The certificate in the box answers a narrower question: this unit, at ambient, held pressure and sealed as declared.

What the Test Pressures Are
For steel and alloy valves, the shell test runs at 1.5 times the cold working pressure rating at 38 °C, rounded up. The high-pressure closure test runs at 1.1 times the same rating. The low-pressure closure test uses air or nitrogen at 5.5 ± 1.5 bar, which is 80 ± 20 psig.
Translated into bar for common classes, a Class 150 carbon steel valve at ambient is rated 19.6 bar, so the shell test is about 29 bar and the closure test about 21.5 bar. Class 300 doubles roughly to 76 bar and 56 bar. This is why a Class 150 valve cannot simply be tested at a Class 300 pressure to "prove" something extra: the test is defined against the rating, not against the pipeline.
Ductile iron and grey iron valves are the exception. API 598 fixes their test pressures by class and size instead of using a multiplier, so applying the steel formula to a ductile iron body produces the wrong number.
How Long Each Test Runs
Hold time is minimum, not target, and it starts only after the specified pressure is reached and stabilised.
NPS | DN | Shell | Backseat | Closure |
2½ – 6 | 65 – 150 | 60 s | 60 s | 60 s |
8 – 12 | 200 – 300 | 120 s | 60 s | 120 s |
14 – 24 | 350 – 600 | 300 s | 60 s | 120 s |
above 24 | above 600 | 600 s | 120 s | 240 s |
Two details cause disputes. First, for a bidirectional valve tested from both sides, the full closure duration applies to each direction; the time is not split. Second, filling the valve, venting trapped air and bringing the pressure up do not count toward the hold.
Soft Seats Must Not Leak at All
For resilient-seated valves — PTFE, RPTFE, PEEK, EPDM, NBR — API 598 allows zero visible leakage in both the liquid and the gas closure test, at every size. A drop is a failure, not a tolerance.
This is the practical consequence of the polymer conforming to the ball or disc. If the seat is correctly moulded, correctly loaded and undamaged, it seals. If it weeps, something is wrong that will get worse in service.
For buyers, this is the most useful line in the whole standard. "Zero leakage, soft seated, API 598" is a testable statement. "Leak-free" is not.
One caveat belongs here. Zero leakage is measured with the valve closed by normal operating force, not by hanging a cheater bar on the handwheel or over-torquing an actuator. A seat that only seals when crushed is a seat that will be crushed again in service, and it will not recover.
Where Metal Seats Are Allowed to Drip
Metal-seated valves are different by physics, not by concession. Lapped metal surfaces cannot close every microscopic gap, so API 598 sets an allowance that scales with size — a few drops per minute at DN50, more at DN600, with gas limits expressed in bubbles per minute.
Two things follow. A metal-seated gate valve tested to zero leakage is either lapped to a standard nobody can repeat in production, or the test was not what the certificate claims. And if the specification calls for ISO 5208 Rate A, which is no visible leakage, that is stricter than API 598's metal-seat table — it must be priced and agreed, not assumed.
The Gas Test Is Often the Harder One
In a floating ball valve or a wedge gate, line pressure helps the closure: the higher the differential, the harder the ball or wedge is pushed into the downstream seat. At 5.5 bar there is very little of that help, so the low-pressure gas test measures whether the seat seals on its own geometry and finish.
Gas also finds paths that water cannot. Valves that look tight in the hydro test routinely bubble in the gas test. For soft-seated valves this test is mandatory up to NPS 4, and it can be specified on larger sizes.
Backseat: The Test That Gets Skipped
The backseat test is the one most often missing from certificates, and the one maintenance teams miss most later. It requires the valve fully open, the packing gland loosened, and 1.1 times the rating applied to the body. Any leakage past the stem means the backseat is not sealing.
Bellows-sealed valves are excluded, because the bellows replaces the backseat function. Everything with a bolted bonnet and a conventional stem should have this test recorded.
The consequence of skipping it appears years later, on a line that cannot be shut down. Without a working backseat there is no safe way to change packing at pressure, and a routine maintenance task becomes a shutdown.
Stainless Steel and the Test Water
This is where material selection meets the test bench, and where stainless valves are quietly damaged by their own acceptance test.
API 598 limits chloride content in hydrostatic test water to 100 ppm for austenitic stainless components. API 6D is stricter at 30 ppm on wetted surfaces of austenitic and duplex valves. Test fluid temperature is capped at 52 °C by ASME B16.34.
The reason is straightforward. A CF8 or CF8M body that sits wet with chloride-bearing water after the test is a pitting corrosion site waiting to start. The valve passed, then corroded in the crate. Practical requirements are a chloride-checked water supply, complete draining after the test, and drying before the flanges are blanked. Where the seat or body has been ground after casting, passivation may be needed before the test, not after.

Carbon Steel: Rust Is the Failure Nobody Tests For
WCB bodies do not pit the way stainless does, but they flash-rust immediately, and the rust travels. Water trapped in the body cavity during the shell test migrates to the seat and the stem threads.
The visual result is a valve that arrives with rust staining at the seat and a buyer who concludes the trim is wrong. Usually the trim is fine and the draining was not. For carbon steel, the specification should include draining, drying and a rust-preventive coating on machined surfaces.
What the Certificate Should Say
A test certificate worth accepting names six things: the standard and its edition, the test pressures actually applied, the hold times, the test medium, the measured leakage against the allowable rate, and the inspector's identity. Without the edition, "API 598" is ambiguous, because the tables have changed between editions.
For critical service — sour, high pressure, ESD or SIL-rated — the test is usually witnessed. Agencies such as Bureau Veritas, Lloyd's Register, SGS, Intertek or TÜV attend against an approved inspection and test plan, and the documentation package carries EN 10204 3.1 material certificates.
Can a valve pass the shell test and fail the seat test?
Yes, routinely. They test different things: the shell contains pressure, the seat closes flow. A leak at the seat does not weaken the body, and a sound body does not seal the seat.
Is the 1.1 times closure test safe for soft seats?
Not always. Excessive differential can deform a polymer seat that would perform correctly at its design differential. This is one reason to state the required closure tests in the purchase order rather than letting the factory choose.
Why does a new stainless valve show rust spots after hydrotesting?
Almost always residual test water with chlorides above the 100 ppm limit, left in the cavity. Rinse with low-chloride water, drain fully and dry before blanking the ports.
Do check valves follow the same closure test?
No. API 598 gives check valves a separate closure duration — 60 seconds even at small sizes — and a separate leakage table, because a check valve seals on flow reversal rather than on applied torque.
The test is the last chance to find a sealing problem while the valve is still in the factory. A certificate that lists pressures, durations and leakage numbers is worth more than a paragraph that says the valve was tested and passed.